Alternators

Generator alternators and alternator components for replacement, repair and upgrades.

Overview

Alternators from Powermec.

The alternator turns the engine’s power into electricity, and the quality of that electricity, steady voltage and frequency, depends on it. Powermec’s Perkins-powered generator sets are built with Mecc Alte, Stamford (Newage) or Leroy-Somer alternators.

We supply brushless, AVR-controlled power-generation alternators for standby, prime and continuous duty, together with the components to repair them. Our technicians test before anything is replaced, so you pay for the fault, not for guesswork.

Genuine Perkins alternators

Charging alternators for every application.

12 V and 24 V Perkins charging alternators for generator-set, industrial, agricultural and construction engines. Select an alternator to see it in detail; our parts team confirms the exact match from your engine serial number.

  • 12 V charging alternator

    For engines on a 12 V electrical system, keeping the starting battery charged and powering the engine’s controls.

    Typical applications

    • Compact and small industrial engines
    • Agricultural and light-duty equipment
    Enquire about this alternator
  • High-output 12 V alternator

    A higher-output, belt-driven alternator for 12 V engines that also run additional electrical equipment.

    Typical applications

    • Engines with extra electrical loads
    • Machines with lighting and accessories
    Enquire about this alternator
  • 24 V heavy-duty alternator

    For engines on a 24 V system, where larger starter motors and longer duty cycles call for a heavier-duty unit.

    Typical applications

    • Generator-set and industrial engines
    • Heavy plant and construction machines
    Enquire about this alternator
  • 24 V compact alternator

    A compact 24 V unit for installations where space around the engine is limited.

    Typical applications

    • Industrial and power-generation engines
    • Enclosed and space-limited installations
    Enquire about this alternator
Genuine Perkins 12 volt, 95 amp charging alternator, rear view
12 V · 95 A12 V charging alternatorFor engines on a 12 V electrical system, keeping the starting battery charged and powering the engine’s controls.
Brushless
AVR-controlled alternator designs
3 makes
Mecc Alte, Stamford and Leroy-Somer
Every duty
Standby, prime and continuous
Test first
Diagnosis before replacement

How an alternator works

From a turning shaft to steady power.

A brushless alternator has five working parts. A fault in any one of them shows up as no voltage, low voltage or unstable voltage.

  1. 01

    The engine drives the rotor

    The engine turns the main rotor at a fixed speed, 1,500 rpm for 50 Hz on a four-pole machine.

  2. 02

    The exciter

    A small generator on the same shaft produces the current that magnetises the main rotor.

  3. 03

    The rotating rectifier

    Diodes on the shaft turn the exciter’s AC into DC for the rotor. One failed diode can cause low or unstable voltage.

  4. 04

    The main stator

    The rotor’s magnetic field induces the output voltage in the stator windings, which feed your load.

  5. 05

    The AVR

    The automatic voltage regulator senses the output and adjusts the exciter to hold voltage steady as the load changes.

Product range

What we supply.

Send your model and serial number and our parts team confirms the correct part and price.

Complete alternators

Power-generation alternators matched to engine output, voltage and frequency.

  • Stamford and equivalent alternators
  • Mecc Alte, Stamford (Newage) and Leroy-Somer
  • Standby, prime and continuous duty

Excitation and control

The parts that create and regulate the magnetic field.

  • AVRs (automatic voltage regulators)
  • Rotating rectifiers and diodes
  • Exciter rotors and stators

Mechanical and windings

For worn, noisy or damaged machines.

  • Bearings
  • Main rotors and stators
  • Terminal boxes and connections

Engine charging alternators

The smaller alternator that keeps the starting batteries charged.

  • Battery-charging alternators
  • Drive belts
  • Regulators

Our services

More than parts on a shelf.

Fault diagnosis

Winding resistance and insulation tests, plus diode and AVR checks, on site or in the workshop.

AVR replacement and setup

Fit the correct AVR and set voltage and stability for your load.

Bearing replacement

Replace worn bearings and check alignment before noise turns into damage.

Rewinds

Rewinding where it is economical; where it is not, we recommend a matched replacement.

Replacement and matching

Alternators sized to engine output, voltage, frequency and load profile.

Load testing

Prove output, voltage regulation and temperature under load after a repair.

Fault guide

Reading the symptoms.

What alternator faults look like, what usually causes them and what we do about it.

SymptomLikely causesWhat we do
No output voltageLost residual magnetism, failed AVR, open-circuit exciter or failed diodesTest the exciter, diodes and AVR, and restore the field if needed
Low voltageAVR setting, a failed diode, or the engine running under speedCheck engine speed first, then the diodes and AVR
Unstable or hunting voltageAVR stability setting, engine speed fluctuation or loose connectionsSeparate engine-speed faults from AVR faults, then adjust or replace
High voltageA failed AVR or a lost sensing connectionShut down to protect equipment, then replace the AVR and check sensing
OverheatingBlocked air vents, overload or unbalanced phase loadsClean the machine and check load and phase balance
Noise or vibrationWorn bearings or misalignmentReplace bearings and check the coupling alignment
Low insulation resistanceMoisture, dust or ageing windingsClean and dry the windings, or rewind if they have broken down

Duty ratings

Matched to how you run your generator.

An alternator is rated for the way it will be used. Telling us the duty is as important as the kVA.

  1. 01

    Standby

    Supplies power only when the mains fails, for a limited number of hours a year.

  2. 02

    Prime

    The main source of power, running for unlimited hours with a load that varies.

  3. 03

    Continuous

    A constant load, running for unlimited hours.

Maintenance advice

Technician tips.

  • Keep alternator vents clear of dust and debris
  • Check insulation resistance during annual service
  • Investigate voltage fluctuations early — they often signal AVR or diode faults

Getting the right part

What to send our parts team.

  • Alternator make, model and serial number, from the rating plate
  • kVA rating, voltage, frequency and number of phases
  • AVR make and model
  • Engine or generator-set make and model
  • The symptoms: no voltage, low, high or unstable
  • Photos of the rating plate and the AVR
  1. 01

    Share your details

    Engine or generator model, serial number and the part you need.

  2. 02

    We confirm fit

    Our parts team checks compatibility, price and stock.

  3. 03

    Collect, deliver or fit

    Collect, arrange delivery, or have our technicians fit it.

FAQ

Common questions.

Can you rewind an alternator?

Yes, where a rewind is economical. Otherwise we recommend a matched replacement.

Why is my voltage unstable?

Common causes are AVR faults, failed diodes or engine speed issues. We diagnose on site or in the workshop.

Which alternator makes do you support?

Our Perkins-powered generator sets use Mecc Alte, Stamford (Newage) or Leroy-Somer alternators. For other makes, send us the rating plate details and we confirm what we can supply.

My generator runs but produces no power. Why?

Usually lost residual magnetism, a failed AVR or failed diodes. We test the excitation system to find which before replacing anything.

Can you replace just the AVR?

Yes, once tests confirm the AVR is the fault. We fit the correct model and set it up for your alternator and load.

Do you supply engine charging alternators?

Yes. We supply the battery-charging alternators, belts and regulators fitted to the engine, as well as the main power-generation alternator.

Plan the next step

Tell us what needs power.

Our team will review the application and route your enquiry to the right solution.